Navigating The Display; View Menu - Bosch Heatronic 4000 Installation & Operating Instructions Manual

4 boiler control, dhw, bacnet and modbus io heatronic 4000 2014/04 en-us
Hide thumbs Also See for Heatronic 4000:
Table of Contents

Advertisement

Navigating The Display

The menu items of the Heatronic 4000 are described in detail in the following pages. The number of available items changes depend-
ing on the control configuration. To find out what other settings affect the display of an item, refer to the menu descriptions.

View Menu

Press
(default display)
& hold
View Menu (1 of 2)
The View Menu includes general information about boiler & pump operation, calls & temperatures. The View Menu is the default
display of the Heatronic 4000.
Item Field
Access: User
Access: User
Access: User
Access: ADV
(-30.0 to 130.0°C)
Access: ADV
(-30.0 to 130.0°C)
Access: User
BTC461503101C | 6720810369 (2018/03)
Setup
Navigate
Source 1
available
Source 2
menus
Source 3
Source 4
Monitor
Monitor 1
Monitor 2
Monitor 3
Monitor 4
Schedule
Time
BAS
Toolbox
Range
TIME
Current date & time.
Requirements: This item is only available when the Setback / Off switch is set to
Setback & Clock (Time menu) is set to ON.
OUTDOOR
---, -76 to 149°F
Current outdoor temperature as measured by the outdoor sensor. "----" is displayed
(-60.0 to 65.0°C)
if there is a sensor fault.
Requirements: This item is only available when Application Mode is set to RSET
or an outdoor sensor is connected.
---, -22 to 266°F
PRIMARY SUPPLY
(-30 to 130°C)
Current primary supply water temperature as measured by the primary supply sensor.
"----" is displayed if there is a sensor fault.
---, -22 to 266°F
BOILER TARGET
(-30 to 130°C)
The boiler target is the temperature the control is trying to maintain at the primary
supply sensor. "----" is displayed when no heat is required.
INDIRECT DHW EXCHANGE TEMPERATURE
---, -22 to 266°F
The indirect DHW exchange target is the temperature the control is trying to
maintain at the boiler 4 outlet sensor. "----" is displayed when no heat is required.
Requirements: This item is only available if Application Mode is set to RSET, SETP
or EMS, IDHW Mode is set to ON & IDHW Location is set to NEAR.
INDIRECT DHW
---, -22 to 266°F
Current indirect DHW tank temperature as measured by the DHW sensor. "----" is
displayed if there is a sensor fault.
Requirements: This item is only available if Application Mode is set to RSET, SETP
or EMS, IDHW Mode is set to ON & IDHW Sensor is set to ON.
Enter
Navigate
selected
available
menu
items
Description
33 of 60
Change
Press
item
once
twice
setting
Heatronic 4000