Setup Menu (1 of 6)
Setup Menu items are used for system specific configuration.
Item Field
Access: INST
Default = 70°F (21.0°C)
Access: INST
Default = 65°F (18.5°C)
Access: INST
Access: ADV
Access: INST
Access: INST
Access: ADV
Access: ADV
Access: ADV
Access: ADV
BTC461503101C | 6720810369 (2018/03)
Range
APPLICATION MODE
RSET, SETP, DDHW,
RSET = Outdoor Temperature Reset
EMS, BAS
SETP = Setpoint Heating
Default = RSET
DDHW = Dedicated DHW Heating
EMS = Energy Management System
BAS = Building Automation System
35 to 100°F
ROOM OCCUPIED
(2.0 to 38.0°C)
The desired room air temperature during the occupied periods.
Requirements: This item is only available if the Application Mode is set to
RSET.
35 to 100°F
ROOM UNOCCUPIED
(2.0 to 38.0°C)
The desired room air temperature during the unoccupied periods.
Requirements: This item is only available if the Application Mode is set to RSET,
Setback / Off switch is set to Setback & a schedule is selected.
BOOST
OFF, 0:20 to 8:00 hrs
The maximum amount of morning boost when change from the unoccupied to
Default: OFF
the occupied period.
Requirements: This item is only available if the Application Mode is set to RSET
& the Setback / Off switch is set to Setback.
OUTDOOR DESIGN
-60 to 45°F
The design outdoor air temperature used in the heat loss calculations for the
(-51.0 to 7.0°C)
space heating system. Typically set to the outdoor temperature of the coldest
Default: 10°F (-12.0°C)
day of the year.
Requirements: This item is only available if the Application Mode is set to
RSET.
TERMINAL UNIT
HRF1, HRF2, COIL,
The type of terminal units that are being used for the space heating system.
Selection includes: high mass radiant floor (HRF1), low mass radiant floor
CONV, RAD, BASE
(HRF2), fancoil (COIL), fin-tube baseboard (CONV), radiator (RAD) & cast iron
Default: CONV
baseboard (BASE).
Requirements: This item is only available if the Application Mode is set to
RSET.
INDOOR DESIGN
35 to 100°F
The design indoor air temperature used in the heat loss calculations for the space
(2.0 to 38.0°C)
heating system.
Default: 70°F (21.0°C)
Requirements: This item is only available if the Application Mode is set to
RSET.
70 to 230°F
PRIMARY DESIGN
The supply water temperature required for the space heating system on the typical
(21.0 to 110.0°C)
coldest day of the year.
Default: 180°F (82.0°C)
Requirements: This item is only available if the Application Mode is set to
RSET.
0-10 or 2-10
EMS SIGNAL
Selects the analog input signal range used with the Energy Management System
Default: 0-10
(EMS).
Requirements: This item is only available if the Application Mode is set to EMS.
-10 to 10°F
EMS OFFSET
(-5.5 to -5.5°C)
Selects the offset from the boiler target temperature interpreted from the EMS
Default: 0°F (0.0°C)
analog input signal.
Requirements: This item is only available if the Application Mode is set to EMS.
Description