Monitor Menu (2 of 2)
Item Field
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
BTC461503101C | 6720810369 (2018/03)
Range
BOILER INLET HIGH
-22 to 266°F
Records the highest boiler inlet temperature since this item was last cleared.
(-30.0 to 130.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a boiler inlet sensor is
connected.
BOILER INLET LOW
-22 to 266°F
Records the lowest boiler inlet temperature since this item was last cleared.
(-30.0 to 130.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a boiler inlet sensor is
connected.
OUTDOOR HIGH
-76 to 149°F
Records the highest outdoor temperature since this item was last cleared. Press
(-60.0 to 65.0°C)
& hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when an outdoor sensor is
connected.
OUTDOOR LOW
-76 to 149°F
Records the lowest outdoor temperature since this item was last cleared. Press
(-60.0 to 65.0°C)
& hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when an outdoor sensor is
connected.
INDIRECT DHW HIGH
-22 to 266°F
Records the highest indirect DHW tank temperature since this item was last
(-30.0 to 130.0°C)
cleared. Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when Application Mode is not set to
BAS, Indirect DHW Mode is set to ON & Indirect DHW Sensor is set to ON.
INDIRECT DHW LOW
-22 to 266°F
Records the lowest indirect DHW tank temperature since this item was last cleared.
(-30.0 to 130.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when Application Mode is not set to
BAS, Indirect DHW Mode is set to ON & Indirect DHW Sensor is set to ON.
DIRECT DHW HIGH
-22 to 266°F
Records the highest direct DHW temperature (primary supply sensor) since this
(-30.0 to 130.0°C)
item was last cleared. Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when Application Mode is set to
DDHW.
DIRECT DHW LOW
-22 to 266°F
Records the lowest direct DHW temperature (primary supply sensor) since this
(-30.0 to 130.0°C)
item was last cleared. Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when Application Mode is set to
DDHW.
FLOW HIGH
-40 to 500°F
Records the highest common flue temperature since this item was last cleared.
(-40.0 to 260.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a common flue sensor is
connected.
FLUE LOW
-40 to 500°F
Records the lowest common flue temperature since this item was last cleared.
(-40.0 to 260.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a common flue sensor is
connected.
Description
47 of 60
Heatronic 4000