Toolbox Menu (1 of 2)
Item Field
Error Display
Access: ---
Access: USER
Access: ADV
Access: USER
Access: USER
Access: INST
Access: INST
Access: INST
Access: INST
Access: INST
Heatronic 4000
Range
ERROR
If an error is present, it will be displayed as the first item in the toolbox menu.
Additional troubleshooting information scrolls on the display. For more information
about error messages, refer to the Error Messages section of this document.
ACCESS LEVEL
USER, INST, ADV
The access level of the control. The access column shows which items are visible
Default: INST
in each access level.
Requirements: This item is only available if the Lock / Unlock switch is set to
Unlock.
OFF, SEL, DONE
DEFAULT
Press the Enter button to show SEL. After 3 seconds DONE will be indicated &
Default: OFF
factory defaults will be loaded to all settings.
4000, Software
TYPE & SOFTWARE VERSION
Version
Product number of the control displayed in the number field. Software version
displayed in the item field.
°F or °C
TEMPERATURE UNITS
Default: °F
Units for display of temperature.
gpm or m³/h
FLOW RATE UNITS
Default: gpm
Units for display of flow rate.
Requirements: This item is only available if Flow Sensor is set to ON.
MBtu or kWh
ENERGY UNITS
Units for display of Energy. If MBtu is selected, the units used for Energy are Therms
Default: MBtu
(THRM). If kWh is selected, the units used for Energy are Gigajoules (GJ).
Requirements: This item is only available if Flow Sensor is set to ON.
psi or kPa
PRESSURE UNITS
Default: psi
Units for display of pressure.
Requirements: This item is only available if Pressure Sensor is set to ON.
BOILER BUS B DEVICES
1 to 24
Displays the number of tN4 devices connected to the Boiler Bus b terminals, tN4
& C0 (32 & 33).
BOILER BUS 1 DEVICES
1 to 24
Displays the number of tN4 devices connected to the Boiler Bus 1 terminals, tN4
& C1 (34 & 35).