JD5003-00
Note the following:
 You should set the Float and Equalize voltages to the values recommended
by your battery manufacturer for 77 °F (25 °C).
 When you enter the Edit Mode to adjust the Float or Equalize voltage (see
Section 2.3.2), the front panel meter displays the 77 °F (25 °C) value for
the Float or Equalize voltage, even if the battery is warmer or cooler than
77 °F (25 °C).
 The actual output voltage of the AT30 may be different from the value
displayed on the front panel meter, if the battery is warmer or cooler than
77 °F (25 °C).
 Use a digital meter to measure the actual dc output voltage of the AT30. If
you know the temperature at the remote TempCo probe, you can use the
graph below to determine that the output voltage is correct.
 If the battery temperature goes below 32 °F (0 °C), there will be no further
increase in charger output voltage. Likewise, if the battery temperature
goes above 122 °F (50 °C), there is no further decrease in output voltage.
1 0 8
1 0 6
1 0 4
1 0 2
N ic ke l-C a d m iu m
1 0 0
9 8
9 6
9 4
2 0
EXAMPLE: Suppose you have a lead-acid battery whose temperature is
100 °F / 37.8 °C. As shown on the graph, the output voltage should be
approximately 97% of the 77 °F voltage. If the float voltage is set on the
front panel to 132 Vdc, the actual output voltage will be:
132 x 0.97 = 128 Vdc

SUPPLEMENTAL DOCUMENTATION

Supplemental documents may be used in conjunction with this application note:
Doc. No.
Online Hyperlink
JA5015-00
http://www.ATSeries.net/PDFs/JA5015-00.pdf
JD5003-00
http://www.ATSeries.net/PDFs/JD5003-00.pdf
JD5003-00.Rev6.doc
O U T P U T V O L T AG E V S B AT T E R Y T E M P E R AT U R E
L e a d -A cid
4 0
6 0
T e m p e ra tu re , D e g re e s F a h re n h e it
Page 8 of 8
AT10.1/AT30 Series Battery Charger
8 0
1 0 0
Description
AT TempCo Probe Accessory Install Instructions
AT Tempco Probe Application Note (this document)
Rev. 6 - Last Printed 10/31/2014 10:31:00 PM
Application Note
E xa m p le :
1 0 0 D e g . F
9 7 % O u tp u t
V o lta g e