 Run the cable though a conduit if possible, but not through a conduit
containing any power wiring.
 Route the other end to the probe at the battery and coil up excess cable.
If the standard (25ft / 7.6m) cable is not long enough, longer cable
assemblies are available in lengths of 50, 100 & 200ft / 15.2, 30.5 &
61.0m. See Appendix B on page 65 for ordering information.
 Be sure your wiring conforms to the NEC and your facility requirements.
5. Attach the interconnection cable to the AT30 as shown in the figure below:
 Route the cable
within the
AT30 enclosure
so it runs with
the wire harness
to the back of
the front panel,
and easily
reaches the
Main Control
PC Board (A1).
 At the Main
Control PC
Board (A1),
insert one of the
bare wires from
the cable into
each terminal of
TB8. Polarity
is not vital.
 Plug the connector at the end of the nylon-shielded wire of the cable
assembly onto J6.
 Using plastic wire ties, fasten the interconnection cable loosely to the
existing wire harness. Make sure that the cable conforms to the service
loop at the hinge end of the door.
6. At the battery, connect the quick-connect terminals to the temperature
compensation probe (A10), or puck. Polarity is not important. Coil up any
excess wire and tape or tie it together to prevent damage.
7. Set jumper (J30) on the Main Control PC Board (A1) to positions 2-3 to use
compensated voltages, or to positions 1-2 to use uncompensated voltages.
JD5003-00.Rev6.doc
AT10.1/AT30 Series Battery Charger
NOTICE
Page 6 of 8
Application Note
Rev. 6 - Last Printed 10/31/2014 10:31:00 PM