Figure 12: Standard Wiring - Pendant Housing - Honeywell HD6 Series Installation Manual

Hide thumbs Also See for HD6 Series:
Table of Contents

Advertisement

3.2 WIRING – STANDARD, CONTINUED
ALIGNMENT TAB
CONTROL DATA
POWER
F1 1.6A 250V
LED POWER INDICATOR
Figure 12: Standard Wiring – Pendant Housing
Rev. 1.02
J4
F1
REMOVABLE TOP PLATE
SPECIFICATIONS
WEIGHT : 6.6 lbs. (3.0 kg) WITH CAMERA
POWER REQUIREMENTS AT DOME: 24VAC, 50/60 Hz, 1.1A
NOTES:
1. TERMINAL STRIPS ACCEPT 18-22AWG WIRE
IF LARGER OR SMALLER WIRE IS REQUIRED, 18-22AWG MUST BE SPLICED
ONTO FIELD WIRE BEFORE INSERTING INTO TERMINAL STRIP.
2. ALL DIMENSIONS IN PARENTHESES ARE IN MILLIMETERS.
3. POWER SOURCE MUST BE 24VAC
24 VAC POWER @1.1A
AWG
22
20
18
16
14
12
4. DATA CABLE SHIELD NOT CONNECTED AT DOME.
ALIGNMENT TAB
TERMINAL STRIP TB1
TB1-1
ALARM TERMINAL
TB1-2
TB1-3
STRIP
TB1-4
TB1-5
TB1-6
TB1-7
VIDEO BNC
TB1-8
CONNECTOR
Jumper W1
Terminated
Position 1 and 2 Last Dome on Data Loop
Unterminated Positions 2 and 3 All Intermediate Domes on Data Loop
Jumper W2
Positions 2 and 3 All Domes
Jumpers W3 & W4
2-wire
Positions 1 and 2 All Domes
±
10% AT POWER SUPPLY.
MAX. DISTANCE TO DOME
65 FEET (19 METERS)
100 FEET (30 METERS)
160 FEET (48 METERS)
260 FEET (79 METERS)
420 FEET (128 METERS)
650 FEET (198 METERS)
28
TERMINAL STRIP TB2
24Vac
TB2-1
Alarm 1
Ground
TB2-2
Common
24Vac
TB2-3
Alarm 2
RX -
TB2-4
Common
RX+
TB2-5
Alarm 3
TX+
TB2-6
Common
TX -
TB2-7
Alarm 4
No Connection
TB2-8
Common
900.0696
1-Aug-06