Functional Overview; Overview; A Variety Of Source Signals; Expandable Module Construction - YOKOGAWA GX60 User Manual

Paperless recorder
Table of Contents

Advertisement

Overview

The GX/GP is a paperless recorder that can display
measured data in real time on its touch screen and save
the data in an SD memory card.
Displaying data on
Universal Viewer
GX/GP
A variety of
signal inputs
Redundant measured data
on internal memory and external media

A Variety of Source Signals

The GX/GP can connect to DC voltage, TC, RTD, ON/
OFF, DC current (mA) and pulse inputs and measure
temperature, flow rate, and other parameters. The GX/GP
acquires data by sampling input signals at the set scan
interval. The shortest scan interval is 1 ms (High-speed AI
module). Up to four alarm conditions can be specified on
each measurement channel.

Expandable Module Construction

The I/O section is modular, so you can configure your
system according to the input types and number of
measurement points.
Modules
Model
Name
GX90XA
Analog input module
GX90XD
Digital input module
GX90YD
Digital output module
GX90WD
Digital Input/Output Module
GX90XP
Pulse Input Module
GX90YA
Analog output module
GX90UT
PID Control Module
• Up to 10 modules can be installed in the GX20/GP20.
• Up to 3 modules can be installed in the GX10/GP10.
• Different modules can coexist.
* Up to nine modules for the GX20/GP20 and two
modules for the GX10/GP10 when an GX60 is
connected.
IM 04L51B01-02EN
Power Specialties, Inc. | www.powerspecialties.com | (816) 353-6550

Functional Overview

GX/GP configuration
and real-time monitoring
on a Web browser
Ethernet
SD memory card
Channels
4/6/10
16
6
Input : 8 ,
Output : 6
10
4
26
Detachable module
terminal block
Maintenance is easy!
GX60 Connection and Multichannel
Measurement
An GX60 I/O can be connected to the GX20/GP20 to
measure up to 450 channels. On the standard type,
you can connect the GX60 to allocate input sections at
different locations.
GX90EX
GX/GP
Rear
GX/GP configuration
Item
Standard Type
Maximum number of
connectable GX60
Maximum number of
10
I/O modules (main
unit + GX60)
Maximum number of
100
I/O channels
1 2 on the rear of the GX10/GP10, 9 on the rear of the
GX20/GP20.
2 9 on the rear of the GX20/GP20.
Max6
GX60
GX/GP
Large Memory Type
6
6
1
2
45
500
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx90exGx10Gx90xaGx90xdGx90ydGx90wd ... Show all