Chapter 1
Overview of Functions
1.1
Input Section
Measurement Channel
Input Type and Computation
IM 04L42B01-01E
• Number of Measurement Channels and Scan Interval
The DX samples the input signals on the measurement channels at the scan interval
to obtain the measured values. The table below shows the relationship between the
number of measurement channels and the scan interval.
Number of
Measurement
Model
Channels
DX2004
4
DX2008
8
DX2010
10
DX2020
20
DX2030
30
DX2040
40
DX2048
48
Integration time of the A/D
converter
* Not available on models equipped with external input channels (/MC1 option) or
when the multi batch function (/BT2 option) is being used.
For the setting procedure, see section 3.1.
• Integration Time of the A/D Converter
The DX uses an A/D converter to convert the sampled analog signal to a digital
signal. By setting the integration time of the A/D converter to match the time period
corresponding to one cycle of the power supply or an integer multiple of one cycle, the
power supply frequency noise can be effectively eliminated.
• Because 100 ms is an integer multiple of 16.7 ms and 20 ms, this setting can be used to
eliminate the power frequency noise for both frequency, 50 Hz and 60 Hz.
• In fast sampling mode, the performance of eliminating power frequency noise is worse than
in normal mode. We recommend that you use normal mode when making measurements in
an environment affected by power frequency noise.
For the setting procedure, see section 3.1.
You can make measurements using the following input types.
Input Type
Description
DC voltage
Measures a DC voltage in the range of ±20 mV to ±50 V.
A shunt resistor *
DC current
to a voltage signal and measured. The measurable range is the range equivalent
to the "DC voltage" range indicated above after converting the current to the
voltage signal.
Thermocouple Measures temperature corresponding to each type: R, S, B, K, E, J, T, N, W,
L, U, and WRe3-25. Measurement is possible on other thermocouples
such as PR40-20 and PLATINEL *
RTD
Measures temperature corresponding to each type: Pt100 and JPt100.
Measurement is possible on other RTDs such as Cu10 or Cu25 *
Ni100 *
2
.
ON/OFF input Displays the contact input or voltage input signals by correlating them to 0% or
100% of the display range.
Contact input: Closed contact is ON (1). Open contact is OFF (0).
Voltage input: Less than 2.4 V is OFF (0). Greater than or equal to 2.4 V is ON (1).
Pulse input *
4
Counts the pulses.
*1 Item sold separately. For example, a 250-Ω shunt resistor is used to convert the signal
to 1 to 5 V for 4-20 mA input.
*2 /N3 option.
*3 /N1 option.
*4 /PM1 option.
Scan Interval
Normal Mode
125 ms
250 ms
1 s, 2 s, 5 s
2 s, 5 s
60 Hz/50 Hz
60 Hz/50 Hz/100 ms
1
is attached to the input terminal. The current signal is converted
2
.
1
2
3
Fast Sampling Mode*
4
25 ms
125 ms
5
600 Hz (fixed)
6
7
8
9
10
11
12
3
and Pt50 or
13
App
Index
1-1