Setting The Auxiliary Alarm Function - YOKOGAWA Daqstation DX2000 User Manual

Hide thumbs Also See for Daqstation DX2000:
Table of Contents

Advertisement

3.5
Setting the Auxiliary Alarm Function
Setup Screen
Setup Items
IM 04L42B01-01E
Set the alarm display and output relays.
For a description of the functions, see section 1.2.
Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the Menu tab > Alarm.
• Basic setting > Reflash
To set the reflash operation on the alarm output relay, select On. The reflash function
is set on the first three output relays.
Setting
Description
Off
Reflash is not used.
On
Reflash is used. The relays are deactivated for approximately 500 ms.
On-1s
Reflash is used. The relays are deactivated for approximately 1 s.
On-2s
Reflash is used. The relays are deactivated for approximately 2 s.
• Basic setting > Rate of change
• Decrease
Set the interval for the rate-of-change calculation of the low limit on rate-of-change
alarm in terms of the number of sampled data points (1 to 32). The actual interval is
obtained by multiplying the value specified here by the scan interval.
• Increase
Set the interval for the rate-of-change calculation of the high limit on rate-of-change
alarm in the same manner as the interval for the low limit on rate-of-change alarm.
• Basic setting > Indicator
You can choose to make the alarm displays behave in the following ways. When you
use the alarm annunciator function (release number 3 or later), the setting follows the
annunciator sequence.
Settings
Description
Nonhold
Clears the alarm indication when the alarm condition is released (returns to
normal condition).
Hold
Holds the alarm indication until an alarm acknowledge operation is performed.
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
3-7