(2) An example of the wiring to external devices in the case of an A1S68DAI is shown
below.
*1: Use two-core shielded wiring (twisted).
*2: If noise or ripple is generated by the external wiring, connect a 0.1 to 0.47μF (25V or
more voltage resistance parts) capacitor to the input terminal of the external device.
Important
A device with a shared current common line cannot be connected to an A1S68DAI.
If such a devices is connected, normal output will not be possible
A1S68DAI
D-A
converter
circuit
D-A
converter
circuit
A1S68DAI
D-A
converter
R
circuit
D-A
converter
R
circuit
*1
CH1
3
4
CH8
17
18
CH1
3
4
CH8
17
18
*2
Motor driver, etc.
0k
to
600k
GND
Motor driver, etc.
0k
to
600k
GND