Table 29. BCU Device ID: DIP Switch Settings
Device ID
S2-1
01
OFF
02
on
03
OFF
04
on
05
OFF
06
on
07
OFF
08
on
09
OFF
10
on
11
OFF
12
on
13
OFF
14
on
15
OFF
16
on
255
OFF
Note:
For the BCU (BMTS), the device ID can be set from 1 to 255 using the DIP switch. For the BCU (BMTW), the device ID can be set
from 1 to 254 using the DIP switch or 1 to 4194303 when softset. To softset the address on a BCU (BMTW), set the DIP switch to
255 (all OFF), then use the IP Validation utility to edit the desired address.
Cycle system power to reset the device ID configuration.
BMTW-SVN01F-EN
DIP Switch Number
S2-2
S2-3
S2-4
on
on
OFF
on
OFF
on
on
OFF
on
OFF
OFF
OFF
OFF
OFF
on
on
on
on
OFF
on
OFF
on
on
OFF
on
OFF
OFF
OFF
OFF
OFF
on
on
OFF
OFF

Network Topology

Topology refers to the various configurations of cables connecting BCUs,
PC Workstations, and hubs within a network. The LAN system supports
bus, star, and bus/star combination topologies. The following sections
describe the installation requirements for these types of topologies.
S2-5
S2-6
on
on
on
on
on
on
on
on
on
on
on
on
on
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
on
OFF
OFF
OFF
OFF
Network Topology
S2-7
S2-8
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
OFF
OFF
151