44
R-Series v5 Instruction Manual
e. Type in the desired Threshold Value (any number between -999.0 ~ 999.0 is valid).
f. Type in the desired Clear Delay time in seconds. Any value other than "0" means
that once this Event is tripped, the measurement must return to normal for this many
seconds before the Event will clear and reset. Clear Delay can be up to 14400
seconds (4 hours).
g. Type in the desired Trip Delay time in seconds. Any value other than "0" means
that the measurement must exceed the threshold for this many seconds before the
Event will be tripped. Trip Delay can be up to 14400 seconds (4 hours).
h. Latching Mode: If enabled, this Event and its associated Actions (see Figure 3-10)
remain active until the Event is acknowledged, even if the measurement
subsequently returns to normal.
i. Valid Time decides when an Alarm notification can be sent. Valid Time is set by
clicking the Add/Modify icon and setting the days and time ranges notifications will
be sent. Then clicking Save.
j. The Invert Valid Time check box inverts the selected Valid Time setting.
GM1196 R-Series v5 Instruction Manual
NOTE
Only one valid time can be selected per alarm.
Figure 3-10 Add Event Time