LOW-PROFILE VENT TERMINATION INSTALLATION

This water heater is certified for sidewall direct venting with IPEX
System 636 Low Profile Vent Kit. Follow instructions below for
proper installations.
All termination kits must be located and installed in accordance
with local building code and
.
Installation Code
1. Once the proper location has been determined, cut two holes
in the wall large enough to accommodate the pipe. See the
(page 34) for pipe diameters and distance between
Table 12
hole centers.
2. Slide both the intake and exhaust pipes through the holes.
Solvent cement both pipes to the base of the vent termination
kit, follow the solvent cementing procedures outlined in the
IPEX System 636 Installation Guide
www.ipexinc.com.
3. To fasten the base to the wall, use the supplied screws and
anchors. A 3/16" (5 mm) hole, that is 1-3/16" (30 mm) deep,
will need to be drilled for the anchors. Locate the anchor hole
using the base as a template.
4. Screw the cap to the base using the supplied screws.
5. Once the vent termination and pipes are secured, the wall
penetrations will need to be sealed from the interior using a
PVC-compatible sealant material.
6. All vent pipes and air inlets must terminate at the same height
to avoid the possibility of severe personal injury, death, or
substantial property damage.
7. Operate the heater through one heat cycle to ensure
combustion-air and vent pipes are properly connected to the
concentric vent termination.
Air Inlet
Piping
Vent (Exhaust)
Piping
Figure 39. Inlet and Vent Flow in Low-Profile Vent Installation
Kit Number
100086241
100187887
100187888
CSA B149.1 Natural Gas and Propane
, which is available on the web
Vent Base
Vent Cap
Table 12. Low Profile Termination Kits - Dimensions
IPEX
Part Number
196984
2" Flush Mount Vent Kit
196985
3" Flush Mount Vent Kit
196986
4" Flush Mount Vent Kit
Table 13. Contents of Low Profile Termination Kit
Qty
1
1
8
4
From Heater Vent
Pipe Connection
Possible Orientations
Figure 40. Low-Profile Vent Clearances
Vent (Exhaust)
Figure 41. Multiple Low-Profile Vent Clearance
Pipe Outside
Description
Diameter
2.375"
3.5"
4.5"
Item Description
Base (two holes)
Cap (one hole)
Stainless Steel Screws
Plastic Anchors
34
To Heater Intake
Air Connection
Vent/Air
Termination
Grade or
Snow Line
12" Min between Edge of Air Inlet
and Adjacent Vent (Exhaust) Outlet
Air Inlet
Vent/Air
Termination
Hole Spacing
(Center to Center)
5.63"
5.63"
5.63"
12"
Min to
Over-
Hang
12"
Min