Shu tdo w n /Di s a s s e mb l y
Authorised electrician
11

Shutdown/Disassembly

11.1

Shutting down the inverter

DANGER
Lethal voltages are still present in the terminals and leads of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death if the leads and terminals in the inverter are touched.
When there is irradiance, DC voltage is present on the open ends of the DC leads. Arcing may occur
if the DC leads are disconnected while under a load.
It is absolutely necessary that the shutdown sequence be carried out in the correct order.
After shutdown, wait at least 30 minutes before working on the inverter.
When working on photovoltaic modules, in addition to disconnecting from the grid, always
disconnect the DC main switch on the generator junction box (or the DC plug connectors).
Disconnecting the grid voltage is not enough.
Shutdown sequence
1.
Switch off the grid voltage by deactivating the external circuit breakers.
2. Disconnect the PV generator using the DC disconnector.
DANGER! The DC leads remain live.
 Ensure that there is no voltage present on the grid connection terminals.
11.2

Deinstalling the inverter

↻ Shut down the inverter.
1.
Open the connection area.
2. Remove the interface cable.
3.
Detach DC connection plug.
4. Detach AC connection leads for the connection terminals.
5.
Open the cable fi ttings.
6. Pull out the leads.
»
The deinstallation of the inverter is complete. Continue with dismantling.
11.3

Dismantling the inverter

↻ Shut down the inverter.
↻ Deinstall the inverter.
1.
Detach screw from the detachment protector.
2. Take the inverter down from the mounting plate.
3.
Securely pack the inverter if it is to be further used,
or
have the inverter professionally disposed of (see chapter 12 on page 52).