Connect the Distributed Modular I/O Master Block

1. Using an M12 D-coded EtherNet/IP cable, connect the block to the Ethernet network.
1
2. Power up the block using 24VDC and a 7/8" 4pole connector wired according to the below diagram.
3. Set the IP address of the block using the pushbutton display. For instructions on operating the display, see the manual.
Port 0
00
Port 1
02
Port 2
IO-Link 1
04
Port 3
IO-Link 2
06
Network
Pushbutton Display
IP address subnet mask
gateway
Aux Power
Port 4
01
08
09
Port 5
03
10
11
Port 6
IO-Link 3
13
05
12
Port 7
IO-Link 4
07
14
15

M12 Network Port

Pin
Function
Description
1
TX +
Transmit Data +
2
RX +
Receive Data +
3
TX -
Transmit Data -
4
RX -
Receive Data -

7/8" Auxiliary Power Port

Pin
Function
Description
1
+ 24 V
Actuator Supply
2
+ 24 V
Sensor/Bus Communication Supply
3
0 V
Sensor/Bus Communication Supply
4
0 V
Actuator Supply

M12 I/O Port

Pin
Configurable Port
IO-Link Port
1
+ 24 V
+ 24 V
2
Input 2 or Output 2
Input/Output 2
3
0 V
0 V
4
Input 1 or Output 1
IO-Link or Input/Output 1
5
FE
FE
2