Unit Installation; Unit Hanging - Daikin FCRN50EXV1 Installation Manual

Ceiling cassette r410a split type air conditioner e series
Hide thumbs Also See for FCRN50EXV1:
Table of Contents

Advertisement

Ensure a location where:
a)
Drainage can be done easily.
b)
Convenient for wiring and piping.
c)
Which have enough space for installation and service work.
d)
Where no risk of flammable gas leakage.
e)
When free from any obstacles in path of cool air discharge and warm air return and must allow spreading of air
throughout the room (near the center of the room).
f)
Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.
g)
The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying
noise and vibration.
h)
The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or
more.
i)
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

Unit Installation

Ceiling Opening Size = 890mm
Hanging Rod Size = 790mm
Unit size 820mm
Unit

Unit Hanging

1 IM-5CKE-0912(0)DAIKIN-EN.indd 6
1 IM-5CKE-0912(0)DAIKIN-EN.indd 6
Piping Direction
Indoor Unit
Ceiling
Board
30 mm
Measure and mark the position for the hanging rod.
Drill the hole for the angle nut on the ceiling and fix the
hanging rod.
The installation template is extended according to
temperature and humidity. Check on dimensions in use.
The dimensions of the installation template are the same
as those of the ceiling opening dimensions.
Before ceiling laminating work is completed, be sure to
fit the installation template to the indoor unit.
NOTE
Be sure to discuss the ceiling drilling work with the
installers concerned.
Hold the unit and hang it on the hanging rod with the nut
and washer.
Adjust the unit height to 30mm between the indoor unit
bottom surface and the ceiling surface.
Confirm with a level gauge that the unit is installed
horizontally and tighten the nut and bolt to prevent unit
falling and vibration.
Open the ceiling board along the outer edge of the paper
installation template.
1-6
9/28/12 4:27:24 PM
9/28/12 4:27:24 PM