APPLICATION
The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat
pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications.
Model
Power Method
T8611G2051
Hardwired
Table 2. T8611 Zoning Applications.
Model
TotalZone
T8611G2051
Yes
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
® U.S. Registered Trademark
Copyright © 2003 Honeywell •
Heat Pump Thermostat
Table 1. Description of T8611 Thermostats.
Changeover
Automatic or manual
®
EMM-3U
EMM-3
Yes
No
• All Rights Reserved
T8611G Chronotherm
System Selection
Heat-Off-Cool-Auto-Em. Heat
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 1.5m (5 ft) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
Position wallplate horizontally on the wall or on a
2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even
when not level.
2. Use a pencil to mark the mounting holes.
See Fig. 2.
Deluxe Zoning
INSTALLATION INSTRUCTIONS
®
Fan Selection
On-Auto
69-1414-2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T8611G Chronotherm and is the answer not in the manual?

Questions and answers

Summary of Contents for Honeywell T8611G Chronotherm

  • Page 1: Wallplate Installation

    INSTALLATION INSTRUCTIONS APPLICATION The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications. Table 1. Description of T8611 Thermostats.
  • Page 2 ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT 3. Remove the wallplate from the wall and drill two 3/16 inch (76 mm holes) in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
  • Page 3: Mounting Thermostat

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT TZ-4 THERMOSTAT CONNECTORS NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL; C7089B OUTDOOR ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON TEMPERATURE THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL. SENSOR (OPTIONAL) CONNECT O/B JUMPER ON TZ-4 PANEL WHEN O/B TERMINAL ON THERMOSTAT IS CONFIGURED AS O.
  • Page 4: Using Thermostat Keys

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT INCREASE TEMPERATURE SET RETURN TIMES SET LEAVE TIMES SET WAKE TIMES INCREASE TIME SETTING SETTING OR SCROLL AND SETPOINTS AND SETPOINTS AND SETPOINTS OR SCROLL FORWARD FORWARD THROUGH THROUGH INSTALLER SETUP INSTALLER SETUP OPTIONS...
  • Page 5: Installer Setup

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT INSTALLER SETUP The Installer Setup is used to customize the thermostat — To exit the Installer Setup, press Run Program. to specific systems. Some of the options include temperature display, changeover, and outdoor temperature display.
  • Page 6 ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT Table 4. Thermostat Installer Setup Options. (Continued) Installer Setup Other Choices Number (Press Factory Setting (Press key to change) Time ∆ key to Actual Select change) Display Description Display Description Setting Degree...
  • Page 7 ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT Table 4. Thermostat Installer Setup Options. (Continued) Installer Setup Other Choices Number (Press Factory Setting (Press key to change) Time ∆ key to Actual Select change) Display Description Display Description Setting Temperature...
  • Page 8: Setting Current Day And Time

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT Setting Current Day and Time 1. Press Set Current Day/Time. Set Day/Time NOTE: On initial powerup or after an extended power loss, 1:00 pm flashes on the display until a key Time...
  • Page 9: Installer Self-Test

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT INSTALLER SELF-TEST Use the Installer Self-Test to check the thermostat operation. Refer to Table 5 for a list of the available self-tests. System Wait Set Program Set Day/Time Temporary Setting Em Heat...
  • Page 10: Thermostat Information

    ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT Table 6. Installer System Test Options. (Continued) Keys to Test Press Number Description Fan comes on. Fan turns off. Key Operation Self-Test Time ∆ 60 2 Change from fan to key operation self-test.
  • Page 11 ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT TROUBLESHOOTING GUIDE (TABLE 7) Table 7. Troubleshooting Guide. Symptom Possible Cause Action Display does not Thermostat is not being • Check for 24 Vac between R and C terminals. come on. powered.
  • Page 12 ® T8611G CHRONOTHERM DELUXE ZONING HEAT PUMP THERMOSTAT Table 8. T8611G2051 Sequence of Operation. Selection System Selection Call Energize Display**** AUTO None None None AUTO Fan Symbol None Fan Symbol AUTO COOL None None AUTO COOL or AUTO Cooling O, G, Y...