Electrical - Redring EXPRESSIONS 570 Installation Instructions Manual

Pumped electric shower
Table of Contents

Advertisement

6. The shower is designed to have an open
outlet and should only be used with Redring
recommended fittings.
WARNING: DO NOT FIT A TAP ON THE
SHOWER OUTLET. TAKE CARE TO AVOID
RESTRICTING THE OUTLET OF THE
PRESSURE RELIEF DEVICE. (SHOWN IN
DIAGRAM 2).
Diagram 8
A
B
C
C) Electrical
The electrical installation must be in accordance
with current BS. 7671 (I.E.E. regulations) and/or
local regulations.
1. The shower is designed for a single phase
A.C. electrical supply of:
Model
Expressions 570
(8.5 kW)
Expressions 570
(9.5 kW)
Please check the rating plate on the unit to see
what details apply to your unit.
8
Simply push
in tube to
attach
Tube is
secured in
position
Push in
collet to
release tube
Variant
Rated Voltage
8.5 / 7.8 kW
240 / 230 V
8.5 kW
230 V
9.5 / 8.7 kW
240 / 230 V
9.5 kW
230 V
2. Cable Sizes
Model
Cable Sizes
Exp. 570
6mm
(8.5 kW)
10mm
Exp. 570 (9.5 kW)
10mm
Expressions 570 9.5/8.7kW, 240/230V, version
may be able to use 6mm
Method 1 (clipped direct) is used. The maximum
cable run for all models above will depend upon
site conditions.
REMEMBER TO UPRATE THE CABLE IF IT RUNS
IN THERMAL INSULATION IN A LOFT.
3. In order to provide a means of isolation, the
heater MUST BE permanently connected to
the electricity supply through a double pole
linked switch with a contact gap of 3mm
mounted in a convenient position. We
recommend ceiling switches.
4. Cut back cable as in diagram 10, connect
cable to terminal block making sure that all the
retaining screws are VERY tight and that no
cable insulation is trapped under the screws.
Diagram 9
WARNING: FAILURE TO COMPLY WITH
THESE INSTRUCTIONS COULD RESULT IN A
FAILURE OF THE TERMINAL BLOCK.
Fuse Type
40 A Cartridge Fuse
2
Type 'A' MCB
2
45 A Cartridge Fuse
2
45 A Cartridge Fuse
2
cable if BS 7671:
SCHEMATIC
WIRING
DIAGRAM