Cleaning And Testing The Flame Monitor - Viessmann Vitoflame 100 Service Instructions Manual

Pressure-jet oil burner
Table of Contents

Advertisement

Further details regarding the individual steps

Cleaning and testing the flame monitor

A Flame monitor
Commissioning, inspection, maintenance
Safety check
Burner start with
covered flame
monitor
Burner start with
flame monitor
illuminated by
external source
Burner operation
with simulated
flame tear-off:
cover the flame
monitor during
operation and
leave in this con-
dition
(cont.)
Response
Fault shutdown at the
end of the safety
time
red flashing code,
flashes 2x
Fault shutdown after
max. 40 s
flashes alternately
green-red
Restart followed by a
fault shutdown at the
end of the safety
time
red flashing code,
flashes 2x