Commissioning, inspection, maintenance
Further details regarding the individual steps
Adjusting the air volume
The air volume is preset at the factory. If required, adjust the air volume. For this,
initially adjust the air volume for stage 2 on the blast tube connection.
Starting up the burner may require some fine adjustment.
You should aim for a standard value of 13 % CO
Readjusting stage 2
A Flame tube
B Sensor plate
C Air damper
D Blast tube connection
E Blast tube connection setting
screw
F Locking screw
10
(cont.)
when adjusting the burner.
2
Modify position of sensor plate B inside
flame tube A by turning blast tube con-
nection setting screw E:
■ Turn clockwise
→ larger cross-section
→ more air
■ Turn anti-clockwise
→ smaller cross-section
→ less air
Note
For standard burner settings, see the
chapter of the same title.