Download Print this page

Specifications - Eaton DeviceNet E50DNA Installation Instructions Manual

Limit switches

Advertisement

111032 Rev --
LED DEFINITIONS AND DIAGNOSTICS
The E50 includes three LED status indicators: Switch state
indication, MAC ID, and network/module status indication.

SPECIFICATIONS

Material of Construction
Zinc Die-Cast Alloy
Enclosure Ratings
IP67
NEMA 3, 3S, 4, 4X, 6, 6P, and 13
Operating Temperature Range
-25° to 70° C (-13° to 158° F)
Storage Temperature Range
-40° to 150° C (-40° to 302° F)
Operating Humidity
<95% RH, non-condensing
Effective 9/97
Module/Network Status LED
MAC ID LED
Switch State LED
LED
Status
MODULE/NETWORK STATUS LED
OFF
Device is neither on-line nor faulted
- Device has not yet completed the Dup_MAC_ID test
- Device may not be powered
Solid
Device is operating properly and properly allocated by a
Green
master.
Flashing
Device is operating properly and on-line but not allocated
Green
by a master.
Flashing
Device has detected a recoverable fault or a connection
Red
is in the timed-out state.
Solid
Device has detected an unrecoverable fault or is in the
Red
communications faulted state.
Flashing
Device is faulted and visibly identifying itself.
Green/Red
Alternately
MAC ID LED
Flashing
The number of blinks is the ten's digit of the
Red
device MAC ID.
Flashing
The number of blinks is the one's digit of the
Green
device MAC ID.
SWITCH STATE LED
Solid Red
Switch mechanism is actuated
OFF
Switch mechanism is not actuated
Operating Voltage
11 to 24 Vdc
Minimum Operational Current
33 mA @ 25 Vdc
Maximum Operational Current
120 mA @ 11 Vdc
Maximum Inrush Current
305 mA @ 25 Vdc
Electromagnetic Compatibility Compliance
Immunity
ESD per IEC 1000-4-2: +/- 8 KV
RFI per IEC 1000-4-3: 50 V/m
EFT per IEC 1000-4-4: 2 kV
Page 5

Advertisement

loading

This manual is also suitable for:

Devicenet e50dnac