Boiler and Heating System Piping
Table 13-1 Minimum Pipe Sizes for Multiple Boiler Applications
FTV110
# of Units
2
1-1/4"
3
1-1/2"
4
5
6
2-1/2"
7
2-1/2"
8
2-1/2"
9
2-1/2"
10
11
12
13
14
15
16
Note: Minimum pipe size based on assumed temperature rise of 25ºF at
maximum firing rate.
56
│
FTV150
Pipe Size
1-1/2"
2"
2"
2"
2"
2-1/2"
2-1/2"
3"
3"
3"
3"
3"
3"
3"
3"
4"
3"
4"
3"
4"
3"
4"
3"
4"
FTV190
2"
2"
2-1/2"
2-1/2"
3"
3"
3"
3"
4"
4"
4"
4"
4"
4"
4"
FTV I&O Manual