Chapter 1. Features and Capabilities
1.4.6 Loads and Forces
For all load and force requirements and limitations, please consult GE.
1.4.7 Description of Different Operating Conditions
Only properly trained personnel are allowed to operate this vessel at the following conditions:
1.4.7a
Startup
The Sentinel LCT4 does not have any specific startup requirements once it has been fastened into the piping system.
Power should be supplied in accordance with local and national electrical codes. The line does not need to be full of
fluid for the system to be powered on.
1.4.7b
Normal Operation
This pressure vessel is intended to measure fluid flow under normal operation. There are no moving parts. The
transmitter will make continuous measurements of the flow along with ancillary inputs of temperature and pressure for
density compensation. The transmitter will output readings through any of several available output options (4-20mA,
pulse out, Modbus, HART, etc.). If any errors occur they will be reported out as well.
1.4.7c
Shutdown
While the Sentinel LCT4 is intended for continuous service there are occasions where shutdown is required. There are
no special requirements specific to this product for shutdown. The system should be de-energized prior to
troubleshooting and any pressure build-up should be relieved per the procedure in the GE Installation Manual
(916-137), Section 5.
1.4.7d
Troubleshooting
Refer to Chapter 7, Troubleshooting, for a list of error codes and troubleshooting steps. For any other inquiries or
assistance with troubleshooting, please consult GE.
20
Sentinel™ LCT4 User's Manual
Need help?
Do you have a question about the Sentinel LCT4 and is the answer not in the manual?