Blower Speed Adjustments - Lennox CB29M Installation Manual

Elite series multi-position blower coils
Table of Contents

Advertisement

Blower Speed Adjustments

Minimum Blower Speeds (With Electric Heaters)
For the minimum allowable speed for the CB29M/CB30M
series units with electric heat, refer to the ECB29 installa-
tion instructions.
Air Volume Adjustment
Blower speed selection is accomplished by changing the
taps at the harness connector at the blower motor. See fig-
ure 10. Refer to unit wiring diagram in figure 11. Refer to
Tables 3 through 20 for blower performance data.
External Static
External Static
Pressure
in. w.g.
Pa
.00
0
.05
10
.10
25
.15
35
.20
50
.25
60
.30
75
.40
100
.50
125
.60
150
.70
175
.75
185
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
External Static Pressure
in. w.g.
Pa
.00
0
.05
10
.10
25
.15
35
.20
50
.25
60
.30
75
.40
100
.50
125
.60
150
.70
175
.75
185
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
504719M 09/05
CB29M-21/26 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
cfm
L/s
Watts
700
330
245
690
325
240
680
320
235
665
315
230
655
310
225
640
300
220
625
295
220
595
280
210
555
260
195
510
240
185
395
185
165
- - - -
- - - -
- - - -
CB29M-31 Blower Performance (208/230V)
Low
cfm
L/s
1015
480
995
470
980
465
960
455
945
445
925
435
900
425
860
405
800
380
740
350
670
315
610
290
Blower Speed Tap Selection
Press the tab to release wire connector.
select connector location for new speed.
Insert wire until it clicks.
Table 3
Medium
cfm
L/s
895
420
875
415
865
410
850
400
830
390
810
385
795
375
750
355
700
330
640
300
- - - -
- - - -
- - - -
- - - -
Table 4
Air Volume and Motor Watts at Specific Blower Taps
Medium
Watts
cfm
L/s
385
1135
535
375
1120
530
365
1095
515
355
1075
505
345
1050
495
335
1025
485
325
1005
475
305
950
450
285
890
420
265
810
385
240
735
345
225
675
320
Page 10
connector
Figure 10
High
Watts
cfm
L/s
310
1030
485
305
1010
475
300
990
470
290
970
460
285
955
450
280
925
440
270
900
425
255
850
400
240
800
380
225
725
340
- - - -
620
295
- - - -
570
270
High
Watts
cfm
L/s
410
1230
580
400
1205
570
390
1190
560
380
1165
550
375
1140
540
365
1105
520
355
1080
510
335
1025
485
315
960
450
290
875
415
270
790
375
255
725
340
harness
Watts
375
370
365
355
350
345
335
320
305
290
265
255
Watts
450
445
440
430
425
415
405
390
370
350
330
315