S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL
The following four tables describe the wiring connections necessary for conversion:
Replacement
Control
Terminal
Function
S8610U
Main Valve
MV
Operator
Main Valve
MV/PV
and Pilot
Common
Pilot Valve
PV
Operator
Burner
GND
Ground
(BURNER)
Connection
Transformer
24V GND
Secondary
(un-
switched
leg)
Transformer
24V *
Secondary
(switched
leg)
TH-W
Flame
d
SENSE
Sensor
Igniter /
SPARK
Sensor
a
Terminals may be marked 25V on some models and 24V on later models. These are functionally equivalent.
b
If 25V (2) and TH-R have wires connected, disconnect and splice together with solderless connector.
c
If TH-R and TH-W are jumpered together, connect 25V (2) lead from S86 to TH-W on S8610U.
d
On dual igniter and sensor models, remove jumper wire quick connect from S8610U Remote Sense terminal, then cut jumper wire at
circuit board and discard.
e
Leave black jumper connected.
f
Use Rajah to quick connector adapter (supplied) or cut Rajah connector off ignition cable at module end and attach insulated quick
connect for connection to S8610U.
69-1955
Table 5. Conversion from Honeywell Intermittent Pilot Modules.
S86A,C
S86B,D
MV
MV
MV/PV
MV/PV
PV
PV
GND
GND
25V (2)
25V
25V (2)
25V
b
b
TH-R
TH-R
c
TH-W
TH-W
e
e
f
IGN COIL
IGN COIL
Old Control
S90A,B
S8600A,B,C
S8610A,B,C
S8610U1003
S8620C,
S8660D,J
S8670D,J
S86E,F,G,H
S8680D,J
MV
MV
MV/PV
MV/PV
PV
PV
GND
GND (BURNER)
(BURNER)
a
25V (2)
24V GND
a
25V (2)
*
24V *
25V (2) or 24V used only in systems where plug-in
cable connects damper to module
b
TH-R
TH-W
(This terminal is
c
TH-W
not included on
S90.)
e
SENSE
f
f
IGN COIL
SPARK
8
S8600F,H,M
S8610F,H,M
S8660E,K
S8670E,K
MV
MV/PV
PV
GND (BURNER)
24V GND
24V *
TH-W
d
e
SPARK
Procedural Notes
* IMPORTANT
If the old module had a
vent damper connector but
a vent damper was not
installed, or if it did not
have a vent damper
connector, then connect
the 25V (2) or 24V wire
from the old module to the
TH-W terminal on the
S8610U. Do not use the
24V terminal on the
S8610U.
If the old module had a
vent damper, connect it to
the P1 connector on the
module, and wire the
terminals as indicated in
the table.