Connecting Dc Power - Siemens RUGGEDCOM RS416 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS416:
Table of Contents

Advertisement

Chapter 2
Installing Device
1
3
Figure 5: Terminal Block Wiring
1. Screw-Type Terminal Block
Terminal (-/N)
6. Surge Ground Terminal
4.
Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
For more information, refer to
5.
Install the supplied metal jumper between terminals 2, 4 and 6 to connect the surge ground terminals to the
chassis ground terminal. The surge ground terminals are used as the ground conductor for all surge and
transient suppression circuitry internal to the unit.
6.
Connect the ground terminal on the power source to the chassis ground terminal on the device. For more
information, refer to
DANGER!
Electrocution hazard – risk of death, serious personal injury and/or damage to the device. Make
sure the supplied terminal block cover is always installed before the device is powered.
7.
Install the terminal block cover.
Section 2.2.2

Connecting DC Power

To connect a single high or low DC power supply to the device, do the following:
CAUTION!
Electrical hazard – risk of damage to equipment. Before testing the dielectric strength (HIPOT) in the
field, remove the metal jumper. This metal jumper connects transient suppression circuitry to chassis
ground and must be removed in order to avoid damage to transient suppression circuitry during testing.
NOTE
The screw-type terminal block is installed using Philips screws and compression plates, allowing either
bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable screws, which
must be removed to make connections.
10
4
5
4
5
6
7
6
2. Pluggable Terminal Block
7. Chassis Ground Terminal
Section 2.2.3, "Wiring
Section 2.4, "Grounding the Device"
6
7
4
5
4
3
3. Jumper
4. Positive/Live (+/L) Terminal
Examples".
RUGGEDCOM RS416
Installation Guide
6
5
2
5. Negative/Neutral (-/N)
Connecting DC Power

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ruggedcom rs416p

Table of Contents