Step 5. Disconnect the unit from the power supply before wiring. The standard
configuration for the Uplink CDMAEZ is to leave DIP switches S3 and S4 set to
"OFF" (Input 1 triggered by 9V DC to 12V DC or an open collector). For detailed
wiring instructions and alternative configurations, see pages 8-9.
CAUTION: Do not connect the unit to a receptacle controlled by a switch.
CAUTION: Improper connections at the power connector may result in damage
to the unit.
Step 6. Configure the unit. Set the DIP switches on the front panel of the unit
according to the following table:
FIGURE 1:
Detail of Dip Switch
TABLE 2: DIP SWITCH SETTINGS
S8
S7 and S6
S5
S3 and S4
S2 and S1
6
®
CDMAEZ
Off = Input 4 Normal Operation
On = Input 4 Neg Pulse causes reset
Reserved (set to OFF)
Off = Controllable output via website
On = Normally closed trouble output
S3
S4
Input 1 Type
OFF
OFF
Standard Input
OFF
ON
Pulse Counter
ON
OFF
Timed Bell
ON
ON
Sampled Siren
Reserved (set to OFF)
(INSTALLATION STEPS continued next page)