System Configuration - Omron SYSMAC C20P Installation Manual

Hide thumbs Also See for SYSMAC C20P:
Table of Contents

Advertisement

System Configuration

1-2

System Configuration

CPU
Expansion I/O Unit
Special I/O Units
Depending on your control requirements, you can combine various Units for
a total number of I/O points ranging anywhere from 20 to 148.
A P-type PC consists of a CPU Unit plus one or more of the following Units:
Expansion I/O Units, Analog Timer Units, Analog I/O Units, or an I/O Link
Unit. All of these Units are connected in series with the CPU Unit at one end.
An I/O Link Unit, if included, must be on the other end (meaning only one I/O
Link Unit can be used) and an Analog Timer Unit cannot be used with. The
rest of the Units can be in any order desired. The Units from which P-type
PCs can be built are shown below.
Unit type
C20P
C28P
C40P
C60P
C4K
C20P
C28P
C40P
C60P
Analog Timer Unit
C4K Analog Input Unit
C1K Analog Input Unit
Analog Output Unit
I/O Link Unit
When determining which configuration to use, another factor to consider is
the ease with which I/O points can be assigned. In order to make the process
as simple as possible, it is recommended that a CPU be used which has
more I/O points than the largest Expansion I/O Unit. For example, rather than
combining a C20P CPU with a C20P Expansion I/O Unit, it would be prefer-
able to use a C40P CPU. Similarly, combining a C60P CPU with a C40 Ex-
pansion I/O Unit would be better than using a C40P CPU and a C60P Expan-
sion I/O Unit.
The tables on the following pages show the possible configurations for a
P-type PC. Although the tables branch to show the various possibilities at
any one point, there can be no branching in the actual PC connections. You
can choose either branch at any point and go as far as required, i.e., you can
break off at any point to create a smaller PC System.When implementing a
system there is a physical restriction on the total cable length allowable. The
sum of the lengths of all cables in the system must be limited to less than 1.2
meters.
The tables also show I/O word allocations for the Units in the systems and
which words will be input words and which words will be output words. All of
these are determined by the position of the Unit in the configuration except
for the C4P and C16P Expansion I/O Units, in which case the model of the
Unit determines whether the words are input or output.
Name
Words
occupied
2
2
4
4
2
2
2
4
4
2
2
2
2
2
Section 1-2
Inputs
Outputs
provided
provided
12 points
8 points
16 points
12 points
24 points
16 points
32 points
24 points
4 input points or 4 output points
12 points
8 points
16 points
12 points
24 points
16 points
32 points
24 points
4 timer inputs
4 analog inputs
1 analog input
1 analog output
16 input and 16 output bits
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c40pSysmac c28pSysmac c60p

Table of Contents