Note
Connect shields together, electrically isolated from the transmitter
Option 3
1. Ground sensor wiring shield at the sensor, if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from
the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
A. Transmitter
B. Sensor wires
Grounded thermocouple inputs
Option 4
1. Ground sensor wiring shield at the sensor.
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from
the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
A. Transmitter
B. Sensor wires
A
B
D
C. PROFIBUS loop
D. Shield ground point
A
B
D
C. PROFIBUS loop
D. Shield ground point