Download  Print this page

Specifications - Mitsubishi Electric FR-A7AZ Instruction Manual

700 series bipolar analog output function high resolution analog input function motor thermistor interface.
Hide thumbs

Advertisement

(2) Measures of inverter
⋅ If a large value is set in Pr. 72 PWM frequency selection, decrease the Pr. 72 setting. (Noise from the motor
increases.)
⋅ Increase the setting of speed (torque) setting filter Pr. 822, Pr. 832 (Pr. 826, Pr. 836) .
CAUTION
As changing the speed (torque) setting filter will affect the response level of the inverter to the command,
adjust the setting by looking at the machine movement.
(3) Measures of option
⋅ Install the line noise filter FR-BLF (FR-BSF01 for the 3.7K or lower).
REMARKS
⋅ Refer to the Inverter Manual for details of measures for EMI.
5.5

Specifications

Frequency setting resolution ..... 0.01Hz/0 to 60Hz (-10 to +10V)
Torque setting resolution ........... 0.024%/0 to 100% (-10 to +10V)
Input resistance......................... 10kΩ
Maximum input voltage ............. ±20VDC
(0.015Hz/0 to 60Hz when option is not mounted)
(0.1%/0 to 100% when option is not mounted)
HIGH RESOLUTION ANALOG INPUT
5
29

Advertisement

Table of Contents