Event Recorder (Er); Application; Design; Technical Data - ABB REL 551-C1*2.5 Technical Reference Manual

Protect line differential protection terminal
Table of Contents

Advertisement

4
4.1
4.2
4.3

Event recorder (ER)

Event recorder (ER)

Application

Use the event recorder to obtain a list of binary signal events that occurred during the distur-
bance.

Design

When a trigger condition for the disturbance report is activated, the event recorder collects time
tagged events from the 48 binary signals that are connected to disturbance report and lists the
changes in status in chronological order. Each list can contain up to 150 time tagged events that
can come from both internal logic signals and binary input channels and up to ten disturbances
can be recorded. Events are recorded during the total recording time which depends on the set
recording times and the actual fault time.
Events can be viewed via SMS and SCS.

Technical data

Table 115: ER - Event recorder
Function
Event buffering capacity
Max. number of events/disturbance report
Max. number of disturbance reports
Chapter 8
Monitoring
Value
150
10
103