ABB REL 551-C1*2.5 Technical Reference Manual page 100

Protect line differential protection terminal
Table of Contents

Advertisement

Event function (EV)
Parameter
Range
T_SUPR11
0.000-60.000
Step: 0.001
T_SUPR13
0.000-60.000
Step: 0.001
T_SUPR15
0.000-60.000
Step: 0.001
NAMEy
0-16
PrColnn
0-7
PrCoInn
0-3
INTERVAL
0 - 60
Step: 1
BOUND
0, 1
FuncTEVnn
0-255
Step: 1
InfoNoy
0-255
Step: 1
EventMasky
No events,
OnSet, OnRe-
set,
OnChange,
Double Ind.,
Double Ind.
with midpos.
Default
Unit
Description
0.000
s
Suppression time for event input 11 and 12.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 13 and 14.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 15 and 16.
Can only be set using the CAP 540 configu-
ration tool.
EVnn-INP-
Char
User name of signal connected to input y,
UTy
y=01-16. String length up to 19 characters.
Can only be set using the CAP 540 configu-
ration tool.
0
-
Protocol for event block nn (nn=01-06). 0:
Not used, 1: SPA, 2: LON, 3: SPA+LON, 4:
IEC, 5: IEC+SPA, 6: IEC+LON, 7:
IEC+LON+SPA. Range valid only for blocks
EV01-EV06. Can only be set from CAP 540
configuration tool.
0
-
Protocol for event block nn (nn=07-44). 0:
Not used, 1: SPA, 2: LON, 3: SPA+LON
Range valid only for blocks EV07-EV44. Can
only be set from CAP 540 configuration tool.
0
s
Cyclic sending of data. Can only be set from
CAP 540 configuration tool.
0
-
Event connected to other terminals on the
network, 0: not connected, 1: connected.
Can only be set from CAP 540 configuration
tool.
0
-
Function type for event block nn (nn=01-06),
used for IEC protocol communication. Only
present in blocks EV01-EV06.
0
-
Information number for event input y,
y=01-16. Used for IEC protocol communica-
tion. Only present in blocks EV01-EV06.
No events
-
Event mask for input y, y=01-16. Can only be
set from PST.
Chapter 7
Logic
91