78
Thermal phase overload protection (THOL)
Table 89:
Settings for the thermal overload protection THOL (THOL-) function
Parameter
Range
Operation
Off,
NonComp,
Comp
IBase
10-200
Step: 1
TBase
0-100
Step: 1
tau
1-62
Step: 1
TAlarm
50-150
Step: 1
TTrip
50-150
Step: 1
TdReset
5-30
Step: 1
Table 90:
Settings for thermal overload protection (THOL), mA input
Parameter
Range
MI11-I_Max
-25.00-25.00
Step: 0.01
MI11-I_Min
-25.00-25.00
Step: 0.01
MI11-I_MaxValue
-1000.00-100
0.00
Step: 0.01
MI11-I_MinValue
-1000.00-100
0.00
Step: 0.01
Default
Unit
Description
Off
-
Operating mode for THOL function
100
% of I1b
Base current
50
ðC
Temperature rise at base current
30
min
Thermal time constant
80
ðC
Alarm level
100
ðC
Trip level
10
ðC
Trip hystereses
Default
Unit
Description
20.00
mA
Max current of transducer to Input 1
Can only be set from PST
4.00
mA
Min current of transducer to Input 1
Can only be set from PST
20.00
ðC
Max primary value corr. to I_Max, Input 1
Can only be set from PST
4.00
ðC
Min primary value corr. to I_Min, Input 1
Can only be set from PST
Chapter 5
Current