Input And Output Signals; Setting Parameters - ABB REL 551-C1*2.5 Technical Reference Manual

Protect line differential protection terminal
Table of Contents

Advertisement

1.4
1.5
Disturbance report (DRP)

Input and output signals

Table 103: Input signals for the DISTURBREPORT (DRPn-) function blocks
Signal
CLRLEDS
INPUT1 - INPUT48
NAME01-48
FuncT01-48
InfoNo01-48
Path in local HMI: ServiceReport/Functions/DisturbReport
Table 104: Output signals for the DISTURBREPORT (DRP1-) function block
Signal
OFF
RECSTART
RECMADE
MEMUSED
CLEARED

Setting parameters

Path in local HMI: Settings/DisturbReport/Operation
Table 105: Parameters for disturbance report
Parameter
Range
Operation
Off, On
PostRetrig
Off, On
Path in local HMI:Settings/DisturbReport/SequenceNo
Table 106: Parameters for sequence number
Parameter
Range
SequenceNo
0-255
Step: 1
Path in local HMI: Settings/DisturbReport/RecordingTimes
Description
Clear HMI LEDs (only DRP1)
Select binary signal to be recorded as signal no. xx were xx=1 - 48.
Signal name set by user, 13 char., for disturbance presentation
Function type, set by user ( for IEC )
Information number, set by user ( for IEC )
Description
Disturbance Report function turned off
Disturbance recording started
Disturbance recording made
More than 80% of recording memory used
All disturbances in Disturbance Report cleared
Default
Unit
Description
On
-
Determines if disturbances are recorded
(on) or not (off).
Off
-
Determines if retriggering during the post-
fault recording is allowed (on) or not (off).
Default
Unit
Description
0
-
Allows for manual setting of the sequence
number of the next disturbance.
Chapter 8
Monitoring
97