Transformer Module (Trm); Design; Technical Data - ABB REL 551-C1*2.5 Technical Reference Manual

Protect line differential protection terminal
Table of Contents

Advertisement

3
3.1
3.2
140

Transformer module (TRM)

Transformer module (TRM)

Design

A transformer input module can have up to 10 input transformers. The actual number depends
on the type of terminal. Terminals including only current measuring functions only have current
inputs. Fully equipped the transformer module consists of:
Five voltage transformers
Five current transformers
The inputs are mainly used for:
Phase currents
Residual current of the protected line
Residual current of the parallel circuit (if any) for compensation of the effect of
the zero sequence mutual impedance on the fault locator measurement or residual
current of the protected line but from a parallel core used for CT circuit supervi-
sion function or independent earth fault function.
Phase voltages
Open delta voltage for the protected line (for an optional directional earth-fault
protection)
Phase voltage for an optional synchronism and energizing check.

Technical data

Table 161: TRM - Energizing quantities, rated values and limits
Quantity
Current
Operative range
Permissive overload
Burden
Frequency
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Rated value
I
= 1 or 5 A
r
(0.004-100) x I
r
4 × I
cont.
r
100 × I
*)
for 1 s
r
< 0.25 VA at I
= 1 or 5 A
r
f
= 50/60 Hz
r
Chapter 10
Hardware modules
Nominal range
(0.2-30) × I
r
(0.2-15) x I
for line differential
r
function
+/-10%

Advertisement

Table of Contents
loading

Table of Contents