ABB REL 551-C1*2.5 Technical Reference Manual page 107

Protect line differential protection terminal
Table of Contents

Advertisement

98
Disturbance report (DRP)
Table 107: Parameters for recording time
Parameter
Range
tPre
0.05-0.30
Step: 0.01
tPost
0.1-5.0
Step: 0.1
tLim
0.5-6.0
Step: 0.1
Path in local HMI: Settings/DisturbReport/BinarySignals/Inputn
Table 108: Parameters for reporting of binary signals
Parameter
Range
TrigOperation
Off, On
TrigLevel
Trig on 1, Trig
on 0
IndicationMask
Hide, Show
SetLed
Off, On
NAME
1 - 13
Path in local HMI: Settings/DisturbReport/AnalogSignals/Un
Table 109: Voltage parameters for disturbance recorder
Parameter
Range
Operation
Off, On
<TrigLevel
0-110
Step: 1
>TrigLevel
0-200
Step: 1
<TrigOperation
Off, On
>TrigOperation
Off, On
Path in local HMI: Settings/DisturbReport/AnalogSignals/In
Default
Unit
Description
0.10
s
Prefault recording time
0.5
s
Postfault recording time
1.0
s
Fault recording time limit
Default
Unit
Description
Off
-
Determines if the signal should trigger
disturbance recording
Trig on 1
-
Selects the trigger signal transition.
Hide
-
Determines if the signal should be
included in the HMI indications list
Off
-
Determines if the signal should activate
the red HMI LED
Input n
Char
Signal name used in disturbance report
and indications. Can only be set from the
configuration tool.
( n =1-48)
Default
Unit
Description
On
-
Determines if the analog signal is to be
recorded (on) or not (off).
90
% of Unb
Undervoltage trigger level in per cent of
signal.
110
% of Unb
Overvoltage trigger level in per cent of
signal.
Off
-
Determines if the analog signal's under-
voltage trigger condition should be used
(on) or not (off)
Off
-
Determines if the analog signal's over-
voltage trigger condition should be used
(on) or not (off)
Chapter 8
Monitoring