11.4.3. Air Purging Of The Pipings And Indoor Unit
1) Checking a gas leakage
1. Remove the service port cap from 3-way valves.
2. Connect the Manifold gauge set to the service port of liquid side 3-way valve.
3. Connect the Charging Cylinder to the Manifold gauge set and open the valve of the Cylinder.
4. Open the low pressure side valve of the Manifold gauge for approx.10 seconds and then close.
5. Check gas-leakage of the connecting portion of pipings with the gas-leak detector.
<For the left pipings>
1) Measure the pressure.
2) Keep it for 5-10 minutes.
• Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
2) Air Purging
The air remaining in the Refrigeration cycle which contains moisture may cause malfunction on the Compressor.
1. To purge the air, push the pin on the Gas side 3-way valve for three seconds with a Hexagonal wrench and set it free for one
minute.
• Repeat this for three times.
2. To balance the refrigerant, close the low pressure side valve on the Manifold gauge and release refrigerant from the piping
through service port until the gauge indicates 0.5 -0.3MPa.
3. Set both 3-way valves to open position with the Hexagonal wrench for the unit operation.