Connecting up
5.5 Attachment to Industrial Ethernet
PIN assignment
The following table shows the pin assignment of the M12 sockets:
Pin no.:
1
2
3
4
Permitted cable lengths
● With connection using TP cords or TP-XP cords: maximum 10 m
● When connected using IE FC cable with IE RJ-45 plug:
Depending on the cable type, a total length of up to 100 m is permitted between two
devices.
IE FC M12 plug PRO
The IE FC M12 Plug PRO has a high degree of protection (IP65/67) and is suitable for
connecting the X208PRO to Industrial Ethernet. You can obtain this plug using the following
order number: 6GK1 901-0DB20-6AA0.