Csa - Emerson Fisher 3582i Instruction Manual

Positioners, electro-pneumatic converter, and valve stem position transmitter
Table of Contents

Advertisement

Instruction Manual
D200138X012

CSA

Intrinsically Safe, Explosion proof, Type n, Dust‐Ignition proof, DIV 2
No special conditions for safe use.
Refer to table 4 for additional information, figure 28 for CSA loop schematics, and figure 29 for a typical CSA/FM
approval nameplate.
Table 4. Hazardous Area Classifications for Fisher 582i Converter
Certification
Body
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591
Ex ia Intrinsically Safe
Class I, II Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28591
Explosion Proof
Ex d IIC T6
CSA
Class I, Division I, GP A,B,C,D T6
Type n
Ex nA IIC T6
Class I, Division 2, GP A,B,C,D T6
Class II, Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6
1.These hazardous area classification also apply to 3582i positioners.
FM
Intrinsically Safe, Explosion proof, Type n, Non‐incendive, Dust‐Ignition proof
No special conditions for safe use.
Refer to table 5 for additional information, figure 30 for the FM loop schematic, and figure 29 for a typical CSA/FM
approval nameplate.
Table 5. Hazardous Area Classifications for Fisher 582i Converter
Certification
Body
Intrinsically Safe
Class I Zone 0 AEx ia IIC T4/T5/T6
per drawing GE28590
Class I, II, III Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28590
Explosion Proof
Class I Zone 1 AEx d IIC T6
FM
Class I, Division I, GP A,B,C,D T6
Type n
Class I Zone 2 AEx nA IIC T6
Class I Division 2, GP A,B,C,D T6
Class II Division 1, GP E,F,G T6
Class II Division 2, GP F,G T6
1.These hazardous area classification also apply to 3582i positioners.
Certification Obtained
Certification Obtained
(1)
—CSA (Canada)
Entity Rating
Temperature Code
Vmax = 30 VDC
T4 (Tamb ≤ 71°C)
Imax = 150 mA
T5 (Tamb ≤ 62°C)
Pi = 1.25 W
T6 (Tamb ≤ 47°C)
Ci = 0 nF
Li = 0 mH
T6 (Tamb ≤ 71°C)
- - -
T6 (Tamb ≤ 71°C)
- - -
T6 (Tamb ≤ 71°C)
- - -
(1)
—FM (United States)
Entity Rating
Temperature Code
Vmax = 30 VDC
T4 (Tamb ≤ 71°C)
Imax = 150 mA
T5 (Tamb ≤ 62°C)
Pi = 1.25 W
T6 (Tamb ≤ 47°C)
Ci = 0 nF
Li = 0 mH
T6 (Tamb ≤ 71°C)
- - -
T6 (Tamb ≤ 71°C)
- - -
T6 (Tamb ≤ 71°C)
- - -
3582, 582i, and 3583
January 2013
Enclosure Rating
CSA Type 3 Encl.
CSA Type 3 Encl.
CSA Type 3 Encl.
CSA Type 3 Encl.
Enclosure Rating
NEMA 3, IP54
NEMA 3, IP54
NEMA 3, IP54
NEMA 3, IP54
9