3582, 582i, and 3583
January 2013
IECEx
Conditions of Certification
Intrinsically Safe
WARNING
Substitution of components may impair intrinsic safety.
-40_C ≤ Ta ≤ +71_C; T6 (Ta ≤ +47_C); T5 (Ta ≤ +62_C); T4 (Ta ≤ +71_C)
Entity Parameters
Ui = 30 V, li = 150 mA, Pi = 1.25 W, Ci = 0 nF, Li = 0 mH
Flameproof
WARNING
Disconnect power before opening.
-40_C ≤ Ta ≤ +71_C; T6 (Ta ≤ +71_C)
Type n
WARNING
Disconnect power before opening.
-40_C ≤ Ta ≤ +71_C; T6 (Ta ≤ +71_C)
Refer to table 7 for approval information and figure 31 for a typical ATEX/IECEx approval nameplate.
Table 7. Hazardous Area Classifications for Fisher 582i Converter
Certificate
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6
IECEx
Flameproof
Gas
Ex d IIC T6
Type n
Gas
Ex nA IIC T6
1.These hazardous area classification also apply to 3582i positioners.
12
Certification Obtained
(1)
—IECEx
Entity Rating
Temperature Code
Ui = 30 VDC
T4 (Tamb ≤ 71°C)
Ii = 150 mA
T5 (Tamb ≤ 62°C)
Pi = 1.25 W
T6 (Tamb ≤ 47°C)
Ci = 0 nF
Li = 0 mH
T6 (Tamb ≤ 71°C)
- - -
T6 (Tamb ≤ 71°C)
- - -
Instruction Manual
D200138X012
Enclosure Rating
IP54
IP54
IP54