Connecting the control cables

Default I/O connection diagram
The default connection of the control signals depends on the application macro in
use, which is selected with parameter
The default macro is the HVAC Default macro. It provides a general purpose I/O
configuration with three constant speeds. Parameter values are the default values
given in chapter Actual signals and parameters in ACS320 user's manual
(3AUA0000062599 [English]).
The default I/O connections for the HVAC Default macro are given in the figure below.
1...10 kohm
max. 500 ohm
1)
See parameter group
SPEEDS:
DI3 Operation (parameter)
0
Set speed through AI1
1
Speed 1 (1202)
0
Speed 2 (1203)
1
Speed 3 (1204)
9902 APPLIC
X1A
1
SCR
Signal cable shield (screen)
2
AI1
External reference: 0...10 V or 0...20 mA
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
PID feedback 0...10 V or 0...20 mA
6
GND
Analog input circuit common
7
AO
Output frequency value: 0...20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Not Configured
14 DI3
Constant speed selection
15 DI4
Safety Interlock
16 DI5
Not Configured
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
12 CONSTANT
Electrical installation 21
MACRO.
1)
Relay output 1
Default operation: Ready
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
Tightening torque: 0.4 N.m (3.5 lbf.in).