B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specified. Framing closer than the
minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc.)
Failure to comply could cause fire.
Note: For non-combustible fireplace finish material (marble,
stone, etc) specifications refer to Section 13.C.
Combustible Mantels
1/2 IN.
Thick Wall
Sheathing
14 IN.
MIN.
Figure 13.5 Clearances To Combustibles Mantels Or Other
Combustibles Above Appliance
Non-combustible Mantels
1/2 IN.
Thick Wall
Sheathing
MEASUREMENT
FROM TOP OF
FIREPLACE
OPENING
See Dimension T on
Appliance Dimension
Diagram (Figure 16.1).
Figure 13.6 Clearances To Non-Combustible Mantels Or Other
Non-Combustibles Above Appliance
54
12 IN.
MAX.
MEASUREMENT
FROM TOP OF
FIREPLACE
OPENING
See Dimension T on Appliance
Dimension Diagram (Figure 16.1).
12 IN.
MAX.
14 IN.
MIN.
1 IN.MIN.
4 IN.
MAX.
Heat & Glo • SLR-D • 2333-900 Rev. F • 9/17
Mantel Legs Or Wall Projections Extending Past The Face
Of The Fireplace (Combustible or Non-Combustible)
6 IN.
MINIMUM
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 16.1).
Figure 13.7 Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
7 IN.
MINIMUM
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 16.1).
Figure 13.8 Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Note: Clearance from opening
to perpendicular wall.
3 FT. MAXIMUM
Note: Clearance from opening
to perpendicular wall.
UNLIMITED