Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
• ALWAYS maintain specified clearances around venting and firestop systems.
• Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
Top Vent - Horizontal Termination
Venting with 1 elbow
H
Maximum
1
V Minimum
SLR-D
90 Elbow
1-1/2 ft.
1 ft.
305 mm
3 ft.
2 ft.
610 mm
5 ft.
3 ft.
914 mm
7 ft.
4 ft.
1.2 m
14 ft.
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
Figure 7.4
457 mm
914 mm
1.5 m
2.1 m
4.3 m
H
1
Heat & Glo • SLR-D • 2333-900 Rev. F • 9/17
WARNING
CAUTION: The SLP-HRC-SS termination cap is not
approved for use with propane (LP) fuel. May lead
to elevated glass temperature that may cause tem-
pered glass breakage.
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
flex vent except when using the
simple up and out installation
(see Figure 7.17).
V
1
25