3 DESCRIPTION

The submersible motor pump MAGNUM S consists of a three-phase submersible motor with connecting cable,
and oil chamber, and the pump housing with cutter and impeller. The electric motor flanged onto the pump
housing has a motor output of 4 / 5.5 / 7.5 / 11 or 15 kW, depending on the respective model.
To motor is equipped with PTC thermistor detectors to protect if from overheating. Therefore the motor
protection will only be effective if the motor connecting cable is linked up not only with a star-delta starter but
also a suitable thermistor trip device.
The control box that is available as motor accessory, includes not only the starting contactor but also the
thermistor trip device. The red alarm lamp lights up when the thermistor tripping device has been actuated
!
NOTE
WARNING!
The motor is sealed by two mechanical seals mounted in series. The mechanical seal on the motor side is
lubricated only by the oil contained in the oil chamber, while the mechanical seal on the impeller side is
lubricated by the pumped medium in addition. The bearing of the SUBMERSIBLE MOTOR PUMP is life-
lubricated.
Apart from pumping liquids into other tanks, the submersible motor pump M S can also be used for stirring the
pit content.
For this type of operation the equipment and fittings such as delivery line, delivery socket and elbow are
replaced by a nozzle with optional 50 or 80 mm diameter mounted on the pump housing.

4 PUTTING INTO OPERATION

When the pump is put into operation for the first time ensure that the supply voltage corresponds with the
voltage specified on the motor nameplate.
Before you connect the motor check the phase sequence for the motor's direction of rotation.
For connecting the motor it is imperative that all regulations applying to electrical equipment as well as all
instructions of the drive manufacturer are strictly observed (e.g. motor protection switch, main disconnect
possibly lockable).
WARNING!
Operating manual BAUER Submersible Motor Pump / Version X-2010
The motor cable should be linked up to the control box only by a qualified
technician.
Check-up must be performed
The wiring diagram is placed inside the control box.
preferably be mounted and tightly screwed under a roof where it is protected from
the weather.
When connecting the system to power supply ensure the connecting cable is amply
dimensioned and the motor's direction of rotation is correct.
Check oil level in the gearbox and in the oil reservoir before every start! (Confer to
Technical Data for type and quantity of oil).
according to the wiring diagram!
The control box should