wattstopper FS-705 Installation Instructions page 3

Wide-angle occupancy sensor passive infrared,low voltage

Advertisement

Line
Neutral
Model #:
BZ-50 Power Pack
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Blue
UL 2043 Plenum Rated
Lighting
White
Power Pack
Red
Neut.
Load
Switch
Black
Red
Hot
APPLIANCE
Black
CONTROL
88T9
RJ45 connection
24VDC
Sensor
Santa Clara, CA • 800.879.8585
Red
FS-C2 shielded 6" (152mm) cable with 3 ying leads at one end and a shielded RJ45 male
connector at the other. Add an FS-C5 coupler and FS-C1 or FS-C3 to extend cable.
Figure 3: BZ‑50 Power Pack connected to FS‑705
using an FS‑C2 adaptor
Line
Neutral
Model #:
BZ-150 Power Pack
120/230/277VAC, 50/60Hz, 225mA output
APPLIANCE
20A ballast or incandescent load
CONTROL
88T9
Set BZ-150
Motor load: 1HP@120/240VAC
Class 2 power supply
White
Power Pack
Red
Lighting
Neut.
Load
UL 2043 Plenum Rated
120VAC
Black
Red
to
Hot
277VAC
Low Voltage Wires
Santa Clara, CA
+12-24VDC In
Orange
Hold ON
Control
Auto-ON
800.879.8585
Common
Any 3-Wire
24VDC
+24VDC
Auto
Manual
Sensor
ON
ON
+12-24VDC In
Hold OFF
Brown
Momentary Switch (optional)
FS-C2 shielded 6" (152mm) cable with 3 ying leads at one end and a shielded RJ45
male connector at the other. Use FS-C5 coupler with FS-C1 or FS-C3 to extend cable.
Figure 4: BZ‑150 Power Pack connected to FS‑705
using an FS‑C2 adaptor
Call 800.879.8585 for Technical Support
Feed-through
Load
Local OFF Switch
FS-705 Sensor
Yellow
Feed-through
Local OFF Switch
FS-705 Sensor
Yellow
Blue
Black
Red
ADJUSTMENTS
The Time Delay and PIR
Sensitivity adjustments are
located on the back of the
FS‑705 under a removable cover.
The sensors are factory preset
for maximum sensitivity and a
30 second time delay.
TEST OCCUPANCY SENSOR
Important, there is an initial warm‑up period:
It may take up to a minute for the sensor to warm‑up during
the initial power‑up. The sensor has an "instant on" feature.
This occurs during installation or after a lengthy power failure
only. As soon as power is supplied to the power pack, the
lights will come on and stay on for approximately 1 minute. If
no movement is detected within that time the lights will turn
off until detection occurs. If movement is detected during the
initial 1 minute then the lights will stay on for whatever time
has been set on the time delay.
1. Turn the time delay to minimum.
2. Move out of the sensor's view. Lights should turn off after
30 seconds.
3. Walk down the aisle. When the first sensor detects motion
the green LED in the sensor will flash and the first cooler's
lights should turn on.
4. Proceed down the aisle, the second cooler's sensor should
detect you, the green LED in the sensor will flash and the
second cooler's lights should turn on.
5. This process should continue down the rest of the aisle.
As you walk down the aisle, the cooler lights should
progressively turn on prior to you walking in front of that
cooler, turning on one at a time as you proceed down the
aisle.
6. Repeat this process from the opposite end of the aisle. No
matter which direction you approach the system should
function in this way.
Load
Switch Settings
Sensitivity
Minimum
Maximum
Time Delay
30 second
1 minute
2 minutes
8 minutes
=ON
=OFF