User Manual
Do not install the SUN2000 on flammable building materials.
Do not install the SUN2000 in an area that stores flammable or explosive materials.
Do not install the SUN2000 in a place where personnel are likely to come into contact with its
enclosure and heat sinks. These parts are extremely hot during operation.
Issue 10 (2017-07-30)
The SUN2000 is protected to IP65 and can be installed indoors or outdoors.
The installation method and position must be appropriate for the weight and dimensions
of the SUN2000. For details, see
The wall must be solid enough to support the weight of the SUN2000.
The cable connection area must face downwards.
Install the SUN2000 either vertically or with a backward lean of a maximum of 15
degrees.
The SUN2000 must be installed at an appropriate height for ease of observation and
operation of the monitoring panel.
The SUN2000 must be installed in a well ventilated environment to ensure good heat
dissipation. When installed under direct sunlight, performance de-rate may be initiated
due to additional temperature rise.
Do not install the SUN2000 on a wall made of gypsum boards or similar materials with
weak sound insulation, to avoid noise disturbance in a residential area.
Ensure that there are no objects within 200 mm of both sides of the SUN2000, and no
objects within 500 mm, 600 mm, and 1000 mm of the top, bottom, and front,
respectively (as shown in
sufficient space for installation.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Technical
Specifications.
Figure
4-2). This is to ensure optimal heat dissipation and