Derating - GE AF-600 FP Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Installation Consideration
3.
Current transducers.
4.
Opto-coupler, brake module.
5.
Internal soft-charge, RFI and temperature
measurement circuits.
6.
Custom relays.
Figure 7.3 Galvanic isolation
The functional galvanic isolation (a and b in drawing) is for
the 24 V backup option and for the RS-485 standard bus
interface.
WARNING
Installation at high altitude:
380–480 V, unit size 1x, 2x and 3x: At altitudes above 6,600
ft [2 km], please contact GE regarding PELV.
380–480 V, unit size 4x, 5x and 6x: At altitudes above
10,000 ft [3 km], please contact GE regarding PELV.
525–690 V: At altitudes above 6,600 ft [2 km], please
contact GE regarding PELV.

7.5 Derating

7.5.1 Purpose of Derating
Derating must be taken into account when using the
adjustable frequency drive at low air pressure (high
elevations), at low speeds, with long motor cables, cables
with a large cross-section or at high ambient temperature.
The required action is described in this section.
7.5.2 Derating for Ambient Temperature
90% adjustable frequency drive output current can be
maintained up to max. 122° F [50°C] ambient temperature.
With a typical full load current of EFF 2 motors, full output
shaft power can be maintained up to 122° F [50°C].
For more specific data and/or derating information for
other motors or conditions, please contact GE.
AF-600 FP Design and Installation Guide
7.5.3 Automatic Adaptations to Ensure
Performance
The adjustable frequency drive constantly checks for
critical levels of internal temperature, load current, high
voltage on the intermediate circuit and low motor speeds.
As a response to a critical level, the adjustable frequency
drive can adjust the switching frequency and / or change
the switching pattern in order to ensure the performance
of the adjustable frequency drive. The capability to
automatically reduce the output current extends the
acceptable operating conditions even further.
7.5.4 Derating for Low Air Pressure
The cooling capability of air is decreased at a lower air
pressure.
At an altitude lower than 3,300 ft [1,000 m], no derating is
necessary, but above 3,300 ft [1,000 m], the ambient
temperature (T
derated in accordance with the diagram shown.
Figure 7.4 Derating of output current versus altitude at T
for unit sizes 1x, 2x and 3x. At altitudes above 6,600 ft [2 km],
please contact GE regarding PELV.
An alternative is to lower the ambient temperature at high
altitudes and thereby ensure 100% output current at high
altitudes. As an example of how to read the graph, the
situation at 6,600 ft [2 km] is elaborated. At a temperature
of 113° F [45°C] (T
current is available. At a temperature of 107° F [41.7°C],
100% of the rated output current is available.
Derating of output current versus altitude at T
unit sizes 4x, 5x and 6x.
DET-768A
) or max. output current (I
AMB
- 3.3 K), 91% of the rated output
AMB, MAX
7
7
) should be
out
AMB, MAX
for
AMB, MAX
7-7