7 Maintenance

Maintenance

Accessories

Application fault
messages
26
7
Maintenance
The TMT 122 temperature DIN rail transmitter has no moving parts and requires minimal sche-
duled maintenance.
Sensor Checkout
To determine whether the sensor is at fault, replace it with another sensor or connect a test sensor
locally at the transmitter to test remote sensor wiring. Select any standard, off-the-shelf sensor for
use with a TMT122 temperature transmitter, or consult the factory for a replacement special sensor
or transmitter combination.
8
Accessories
Commubox FXA 191, PC-Software Commuwin II and ReadWin
IEC 60715 for E+H temperature DIN rail transmitters
®
ReadWin
2000 can be downloaded free of charge from the internet from the following address:
www.readwin2000.com
Please contact your supplier when ordering!
9

Trouble-shooting

9.1

Trouble-shooting instructions

If faults occur after commissioning or during measurement, always start any trouble-shooting
sequence using the following check. The user is led towards the possible fault cause and its rectifi-
cation via question and answer.
9.2

Application fault messages

Application fault messages are shown in the display of the HART
module "DXR 275/375" once the menu point "ERROR CODE" has been selected or in the PC ope-
rating surface of Commuwin II (V9H0 - ERROR
Fault code
0
10
11
12
13
14
CODE).
Cause
No fault, Warning
Hardware fault (unit defective)
Sensor short circuit
Sensor cable open circuit
Reference measurement point defec-
tive
Unit not calibrated
Temperature DIN rail transmitter
®
2000, DIN rail clip according to
®
hand operating
Action/cure
None
Replace DIN rail transmitter
Check sensor
Check sensor
None
Return DIN rail transmitter to
manufacturer