6 Commissioning
22
Function group: BASIC CALIBRATION
Type of sensor
Entry of sensor used:
• V2H0
Sensor type
-10..75 mV
10..400 Ohm
10..2000 Ohm
Pt100 DIN
Pt100 JIS
Pt500
Pt1000
Ni100
Ni500
Ni1000
Polynom RTD
Type B
Type C
Type D
Type E
Type J
Type K
Type L
Type N
Type R
Type S
Type T
Type U
Pt100 DIN
Unit meas. value
Enter engineering units.
• V2H2
Entry: °C
°C
Current output
Enter standard (4 to 20 mA) or inverse (20 to 4 mA) current output signal.
• V2H3
Entry:
4 to 20 mA
Value for 4 mA
Entry: For limits see unit function SENSOR TYPE.
• V2H4
0 °C
Value for 20 mA
Entry: For limits see unit function SENSOR TYPE.
• V2H5
100 °C
Connection
Entry of RTD connection mode
• V2H6
Entry:
7
RTD connection
3 wire
!
Function field is only active on selection of resistance thermometer (RTD) in the unit
function SENSOR TYPE (V2H0)
a. Only for Commuwin II operation matrix
Range start
Range end value
10 Ω
-10 mV
10 Ω
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-60 °C (-76 °F)
-60 °C (-76 °F
-60 °C (-76 °F
-270 °C (-454 °F)
0 °C (32 °F)
0 °C (32 °F)
0 °C (32 °F)
-270 °C (-454 °F)
-210 °C (-346 °F)
-270 °C (-454 °F)
-200 °C (-328 °F)
-270 °C (-454 °F)
-50 °C (-58 °F)
-50 °C (-58 °F)
-270 °C (-454 °F)
-200 °C (-328 °F)
°F
K
4 to 20 mA
20 to 4 mA
2 wire
3 wire
4 wire
Note!
a
.
Temperature DIN rail transmitter
400 Ω
75 mV
2000 Ω
850 °C (1562 °F)
649 °C (482 °F)
250 °C (482 °F)
250 °C (482 °F)
180 °C (356 °F)
150 °C (302 °F)
150 °C (302 °F)
2500 °C (4532 °F)
1820 °C (3308 °F)
2320 °C (4208 °F)
2495 °C (4523 °F)
1000 °C (1832 °F)
1200 °C (2192 °F)
1372 °C (2501 °F)
900 °C (1652 °F)
1300 °C (2372 °F)
1768 °C (3214 °F)
1768 °C (3214 °F)
400 °C (752 °F)
600 °C (1112 °F)